How To Quickly Judge The Motor
Aug 12, 2021
With the development of machinery and equipment manufacturing industry, machinery and equipment manufacturers have stricter quality requirements for three-phase asynchronous motors. In recent years, the motor production technology has become increasingly mature, and it can also be optimized for different industries.
Use a multimeter to measure the DC resistance of the three-phase winding of the motor. The closer the results of the three measurements are, the better. The winding resistance is qualified within 2%. When the difference is more than 10%, the phase with the smaller resistance may have an inter-turn short circuit.
Use a 500v insulation shaker to measure the insulation resistance between phases of the three-phase windings and the insulation resistance to ground (to the chassis). The insulation resistance of the motors stored for a long time should be more than 0.5 megohms. It is a good motor and can be used. More than 0.1 megohm and less than 0.5 megohm indicates that the motor has been damp and can only be used after drying. A low insulation resistance indicates that the insulation has been damaged.
Turn the motor rotor, it should be easy and free, and there is no noise and friction, indicating that the bearing and air gap are normal.
Resistance to ground (high-grade ohm gear): The insulation resistance between the motor winding (three-phase) and the outer casing is generally required to reach 2M or more, and the requirements can be reduced as appropriate for use in humid, acid-base and other environments, and generally not allowed. Below 0.5M.