Protection Of Asynchronous Motors(2)
Aug 08, 2021
Motor protection device The damage of the motor is mainly caused by the overheating of the winding or the reduction of the insulation performance, and the overheating of the winding is often caused by the excessive current flowing through the winding. There are two main types of motor protection: current and temperature detection. Below are some introductions to the products.
(1) The thermal relay utilizes the load current to flow through the calibrated resistive element, causing the bimetal thermal element to bend after heating, so that the contacts of the relay operate before the motor winding is burned out. Its operating characteristics are close to the allowable overload characteristics of the motor windings. Although the accuracy of the action time of the thermal relay is general, it can achieve effective overload protection for the motor. With the continuous improvement and improvement of the structural design, in addition to temperature compensation, it also has the functions of phase failure protection and load unbalance protection. For example, T series bimetal thermal overload relays imported from ABB; 3UA5 and 3UA6 series bimetal thermal overload relays imported from Siemens; JR20 and JR36 thermal overload relays, of which Jn36 is a secondary development product. Can replace the outdated product JRl6 type.
(2) The circuit breaker for motor protection with thermal-magnetic tripping is thermally used for overload protection. The structure and operating principle are the same as those of thermal relays. point on, which eventually causes the circuit breaker to open. The electromagnet has a higher setting value and only operates in a short circuit. Its simple structure, small size, low price, action characteristics in line with current standards, and reliable protection, so it is still widely used recently. Especially small-capacity circuit breakers are particularly significant. For example, the M611 motor protection circuit breaker imported from ABB, the domestic DWl5 low-voltage universal circuit breaker (200-630A), and the S series molded case circuit breaker (100, 200, 400 input).
(3) The electronic overcurrent relay detects the fault current signal through the internal current transformers of each phase, and performs corresponding actions after being processed by the electronic circuit. The electronic circuit is flexible and has various action functions, which can widely meet the protection of various types of motors. Its characteristics are: ① A variety of protection functions. There are three main types: overload protection, overload protection ten phase failure protection, overload protection ten phase failure protection + reverse phase protection. ② Action time can be selected (in line with GBl4048. 4-93 standard). Standard type (class 10): 7.2In (In is the rated current of the motor), 4-1Os action, used for standard motor overload protection, quick action type (10A class): 7.2In, 2-1Os action, used for Submersible motor or compression motor overload protection. Slow-action type (30-level): 7.2In, 9-30s action, used for overload protection of motors with long starting time such as blower motors. ③ Wide range of current setting. The ratio of the maximum value to the minimum value is generally up to 3-4 times, or even larger multiples (1.56 times for thermal relays), especially suitable for occasions where the motor capacity changes frequently (such as mines, etc.). ④ There is a fault display. The fault category is displayed by light-emitting diodes, which is convenient for maintenance.
(4) Solid state relay It is a kind of microprocessor device with various functions developed from a simple electronic device that completes the function of a relay. The cost and price vary by function, and the most complex relays can really only be used in larger, more expensive motors or in critical situations. Its main functions of monitoring, measurement and protection are: ① Maximum starting inrush current and time; ② Thermal memory; ⑤ Long-time acceleration of large inertia loads; ④ Phase failure or unbalanced phase current; ⑤ Phase sequence; ⑥ Undervoltage or Overvoltage; ⑦ Overcurrent (overload) operation; ⑧ Stalled rotor; ⑨ Loss of load (drop in operating current due to broken shaft, broken conveyor belt, or pump air suction); ⑩ Motor winding temperature and load bearing temperature; ⑩ Overspeed or stall . Each of the above information can be programmed into the microprocessor, mainly plus the time limit required to ensure that the power is cut off before the motor is started or damaged during operation. Can also use light-emitting diodes or numbers to display the fault category and cause, and can also output data to an external computer.
(5) The action principle of the circuit breaker for motor protection with electronic tripping is similar to the above-mentioned electronic overcurrent relay or solid state relay. The main functions are: circuit parameter display (current, voltage, power, power factor, etc.), load monitoring (removing or switching on the load according to regulations), various protection features (exponential curve inverse time, I2t curve inverse time, definite time or its combination ), fault alarm, test function, self-diagnosis function, communication function, etc. Products such as M series low-voltage circuit breakers produced by Schneider Electric.
(6) Soft starter The main circuit of the soft starter adopts thyristor, and the protection device that controls its disconnection or connection is generally made into a fault detection module, which is used to complete abnormal fault detection before and after the motor starts, such as phase failure, overheating, short circuit , leakage and unbalanced load and other faults, and issue corresponding action commands. Its characteristic is that the system structure is simple, it can be completed by single-chip microcomputer, and it is suitable for industrial control.